Laserfiche WebLink
. + ' -4- <br />b. Smoke detectors shall be capable of detecting gray smoke having a minimum <br />smoke obscuration of 4% per foot (optical density of 0.0177 per foot). <br />c. On smoke detectors requiring a light source for operation, failure of the <br />light source shall result in an audible trouble signal. The failure of the light <br />source shall not cause an alarm signal. The audible trouble signal shall be produced <br />at least once every minute for seven consecutive days. <br />d. For each smoke detector requiring a light source, at least one spare light <br />source bulb shall be provided with the detector and mounted conveniently in or on the <br />unit or associated control unit. <br />Section 10. Alarm Sounding Devices. <br />a. Each detection device shall cause the operation of an alarm which shall be <br />clearly audible in all bedrooms over background noise levels with all intervening doors <br />closed. The tests of audibility level shall be conducted with all household equipmant, <br />which may be in operation at night, in full operation. Examples of such equipment are <br />window air conditioners and room humidifiers. <br />b. All alarm sounding devices shall have a minimum rating of 85 dBA at 10 feet. <br />Section Il. Control Equipment. <br />a. The control equipment shall be automatically restoring on restoration of <br />electrical power. <br />b. If a reset switch is provided, it shall be a self-restoring type. <br />c. Any alarm silencing switch or an audible trouble silencing switch shall not <br />be provided unless its silenced position is indicated by a readily apparent signal. <br />d. Each detector shall have a means to permit the householder to check the <br />system. <br />Section 12. Type of Circuit. <br />a. This ordinance requires a detector circuit where a break in the wiring will <br />not cause an alaxm signal, but will cause an audible trouble signal, using either a <br />closed loop detector circuit or normally open contact detectors with end of line <br />resistor or equivalent. <br />b. All installation wiring extended from the output side of a power limited <br />supply shall either use conductors and cables approved for use with power limited fire <br />pxotective signaling circuits or be wired in accordance with the requirements for non- <br />power limited fire protective signaling circuits of Article 760 of the National <br />Electrical Code, NFPA No. 70-1975. <br />c. Wire used shall be o£ the solid conductor, non-stranded type. <br />Section 13. Level of Prdtectidn. <br />A basic smoke detector shall be installed to protect each separate sleeping area <br />and at the head of each stairway leading to an occupied area. <br />Section 14. Detect6r Location and Spacing. <br />a. Smoke detectors in rooms with ceiling slopes greater than one-foot rise per <br />8-feet horizontally shall be located at the high side of the room. <br />I