Laserfiche WebLink
§ 1521.11 <br />DWELLING HOUSE CODE <br />30 <br />1521.11 The American Society of Mechanical Engineers. <br />1949 with Rules for Construction of Low Pressure Heating Boilers. <br />addenda 8/8/51 <br />1521.12 Standards of the American Standards Association: Prefix "A." <br />A102-1944 Safety Code for Building Construction. <br />Except that: <br />Subsection 1.8 of Part 9, Scaffolds, shall <br />be considered amended and as amended <br />shall read: <br />"All lumber used in the construction of <br />scaffolds shall be of scaffold grade. or stress <br />grade." <br />A21.4-1939 Specifications for Cement Mortar Lining far Cast-Iron Pipe and <br /> Fittings. <br />A40.1-1935 Cast-Iron Soil Pipe and Fittings. <br />A40.2-1936 Brass Fittings for Flared Copper Tubes. <br />A4D.4-1942 <br />A40.6-1943 Air Gaps and Backflow Preventers in Plumbing Systems. <br />A40.5-1943 Threaded Cast-Iron Pipe for Drainage, Vent and Waste Services. <br />A41.1-1944 Building Requirements for Masonry. <br />A42.1-1950 Specifications for Gypsum Plastering and Interior Lathing and <br />A42,4-1950 Furring. <br />A42.2-1946 Specifications for Portland Cement Stucco and Portland Cement <br />A42.3-1946 Plastering. <br />A62.4-1947 Sizes of Clay Flue Linings. <br />A87.1-1947 Building Requirements for Steel Joist Construction. <br />1521.13 Standards of the American Standards Association: Prefix ")i:' <br />B 2.1-1945 Pipe Threads. , <br />B16.3-1951 Malleable-Iron Screwed Fittings, 150 lb. <br />B16.4-1949 Cast-Iron Screwed Fittings, 125 and 2501bs. <br />B16.12-1942 Cast-Iron'Screwed Drainage Fittings. <br />B16.15-1947 Brass or Bronze Screwed Fittings, 125,1b, <br />B16:18-1950 ~. Cast Brass Solder-Joint Fittings. <br />B31.1-1951 Code for Pressure Piping, <br />1521.14 Standards of the American Standards Association: Prefix "C:' <br />C1-1951 National Electrical Code <br /> (Same as NBFU No. 70 and NFPA No. 70) <br />Except that: <br />(a) Sub-paragraph (b) entitled, Recep- <br />tacle Circuits (Dwelling Occupancies), of <br />Paragraph 2115 of Article 210, shall be con- <br />sidered amended and as amended shall read; <br />"For the small appliance load .in bath- <br />room, kitchen, laundry, pantry, dining room <br />and breakfast room of dwelling occupancies, <br />not more than four appliance receptacle <br />outlets shall be installed on any one ap- <br />pliance circuit. In all other rooms, there <br />shall be not more than six receptacle out- <br />lets per circuit. The conductors of such cir- <br />cuits shall be not smaller than No. 12. Out- <br />lets for clocks maybe provided on the light- <br />ing circuit." <br />(b) Sub-paragraph (a-1) entitled, In <br />Listed Occupancies, of Paragraph 2116 of <br />Article 210, shall be considered as amended <br />by adding at the end thereof; the following: <br />"At least one outlet controlled by a wall <br />switch shall be provided for each habitable <br />room, kitchen, toilet room, and bathroom. A <br />lighting outlet shall be provided at laundry <br />trays, and at boilers, furnaces, and other <br />central heating devices. Three-way switches <br />shall be provided for all stairways to con- <br />trol lighting outlets illuminating such stair- <br />ways." <br />(c) Sub-paragraph (b) entitled, Dwell= <br />ing Type Occupancies, of Paragraph 2124, <br />of Article 210, shall be considered amended <br />and as amended shall read: <br />"In every dining room, hallway, recrea- <br />tion and sun room, one receptacle outlet <br />shall be provided for every 20 linear feet or <br />major fraction thereof of the total distance <br />around the room, and in every other habit- <br />able room, one receptacle outlet shall be <br />provided-#or every 12 linear feet or major <br /> <br />a <br />C <br /> <br />~~ <br />:7 <br />95 <br />Heating Appliances and Systems <br />thereto shall ~be without a damper; provided <br />that this requirement shall not apply to sys- <br />tems where dampers and shutters cannot <br />shut off more than 80 per cent of the duct <br />area. <br />(i) Registers in floor over f urnace. Where <br />registers are installed ir_ the floor over a fur- <br />nace, the register box shall be constructed <br />double with not less than a 4 inch air space, <br />except where the warm air passage is sur- <br />rounded by a cold air passage or where the <br />furnace is oil- or gas-fired and automatically <br />controlled so that the temperature of the de- <br />livered air cannot exceed 150 F. Where but <br />one duplex grating is used for both warm <br />air and return air, the area of the return air <br />intake shall. be at least equal to the warm <br />air outlet of the grating. In no case shall the <br />top of the heater within the furnace casing <br />be closer than 12 inches to combustible con- <br />struction or material. <br />(j) Gravity warm air supply ducts near <br />combustible construction. On gravity warm <br />air heating systems, where supply ducts en- <br />ter afloor, partition, or enclosure of com- <br />bustible construction within a horizontal dis- <br />tance of 6 feet from the furnace, the warm <br />air supply pipe or duct connected thereto <br />shall be arranged so that heated air must <br />travel at least 6 feet from the closest primary <br />heating surface and change direction equiv- <br />alent to at least 90° before entering such <br />floor, partition, or enclosure. <br />(k) Forced warm air supply ducts near <br />combustible construction. On forced warm <br />air heating systems, all warm air supply <br />pipes or ducts directly connected to a fur- <br />nace bonnet or plenum and installed adja- <br />cent to combustible construction shall run <br />horizontally at least 2 feet and shall have not <br />less than one angle or elbow before turning <br />vertically upward; or there shall be ,other <br />provisions approved by the Building Official <br />to protect combustible construction from di- <br />rect heat radiation from the furnace. <br />(1) Forced warm air ducts within com- <br />bustible construction less than 6 feet from <br />furnace. On forced warm air heating sys- <br />tems, portions of warm air supply pipes or <br />ducts which are installed within combustible <br />partitions, walls, or floor construction and <br />are within 6 feet of the closest primary heat- <br />ing surface of the furnace shall have a <br />clearance from combustible material of not <br />less than 1 inch. <br />(m) Horizontal warm air ducts near ceil- <br />ing. Portions of warm air supply pipes or <br />ducts-which -run in the open, such as those <br />which run approximately horizontal and <br />§ 1591.43 <br />near the ceiling, shall have clearances as <br />follows: <br />i. From metal, pipes or ducts to combus- <br />tible material, including plaster on wood <br />lath-not less than 1 inch; <br />ii. From metal pipes or ducts to plaster on <br />metal lath or gypsum lath or other equivalent <br />noncombustible finish attached to combus- <br />tible material-not less than ~/4 inch; <br />iii. From metal pipes or ducts covered <br />with 1/4 inch or more of noncombustible in- <br />sulating material, to combustible material- <br />not less than ~4 inch; <br />iv. From pipes or ducts made of asbestos- <br />cement or equivalent, to combustible mate- <br />rial-~/z that specified for metal pipes or <br />ducts. <br />(n) Entering first Roar. Where warm air <br />supply pipes or ducts enter the floor of the <br />first story, above that in which a furnace is <br />situated, at points more than 6 feet from the <br />closest primary heating surface of the fur- <br />nace measured along the line of heated air <br />travel, they shall be separated from all com- <br />bustible material of the floor construction by <br />at feast 5/16 inch, or the pipe or duct shall <br />be of double wall construction with a con- <br />tinuous air space of not less than 5/16 inch <br />between the inner and outer walls. <br />(o) Enclosed in combustible construction <br />more than 6 f eet f rom f urnace. Where warm <br />air supply pipes or ducts are enclosed in com- <br />bustible partitions, walls, or floor construc- <br />tion and are more than 6 feet from the closest <br />primary heating surface of the furnace meas- <br />ured along the line of heated air travel- <br />i. They shall be installed with an air space <br />of not less than 5/16 inch between pipe or <br />duct and combustible material; or <br />ii. Such pipes or ducts shall be made <br />double with a continuous air space of,not less <br />than 5/16 inch between. the inner and' outer <br />walls; or <br />iii. Such pipes or ducts shall be ~4=inch <br />thick asbestos-cement or equivalent, sepa- <br />rated from combustible material by an air <br />space of not less than ~/s inch. <br />(p) In closets. Where warm air supply <br />pipes or ducts are located in closets they <br />shall be covered with not less than i/4 inch <br />asbestos air-cell or equivalent fire-resistive <br />insulating covering protected against injury; <br />or they shall be made double with an air <br />space of not less than one inch between the <br />inner and outer walls. The air space may be <br />reduced to 5/16 inch provided the outer <br />wall is covered with r_ot less than 12-1b: as- <br />bestos paper. <br />~' <br />